Installation and Servicing
Instructions
Alpha 240XP and 240XE
Wall Mounted, Fan Assisted, Room Sealed, Gas Fired
Combination Boilers
For Technical help or for Service call ...
ALPHA HELPLINE
Tel: (01322) 669443
Goldsel Road,
Swanley, Kent BR8 8EX
Fax: (01322) 615017
Service Listed
Alpha 240XP
G.C. No. 47 532 10
Alpha 240XE
G.C. No. 47 532 11
0051
For use with Natural Gas only
Leave these instructions with the User
856368918.048.png 856368918.049.png 856368918.050.png 856368918.051.png 856368918.001.png
CONTENTS
1
Introduction ....................................... 2
7
Routine servicing ............................... 19
2
Technical data ................................... 3
8
Component replacement ................... 21
3
General boiler information .................. 7
9
Wiring diagrams ................................ 34
4
Installation ......................................... 11
10
Fault finding ...................................... 38
5
Commissioning ................................. 16
11
Short parts list ................................... 43
6
Boiler operation ................................. 18
12
Service history .................................. 44
1
INTRODUCTION
The Alpha 'X' Range of boilers are wall mounted, fan assisted room-sealed combination boilers. Heat output is controlled by a
modulating gas valve.
The boilers, providing both central heating and domestic hot water at mains pressure, are designed for use with a fully
pumped, sealed and pressurised heating system using only Natural Gas .
The boilers are supplied with a pump, diverter valve, pressure relief valve, expansion vessel and pressure gauge fully
assembled and tested.
As supplied, the Alpha 240XP and 240XE boilers will automatically modulate to provide central heating outputs between 9.3
and 23.3 kW (31 700 and 79 500 Btu/h).
The maximum output available for domestic hot water is 23.3 kW (79 500 Btu/h), capable of providing 9.5 litres/min with a
temperature rise of 35°C.
IMPORTANT
It is the law that all gas appliances are installed by a competent person, ie CORGI registered personnel, in accordance with
the following recommendations:-
Gas Safety (Installation and Use) Regulations
All relevant Building Regulations issued by the Department of the Environment
Building Standards (Scotland) (Consolidation) Regulations issued by the Scottish Development Department
Local Water Bye Laws
Health & Safety Document No. 635 (The Electricity At Work Regulations 1989)
The installation should also be in accordance with the following British Standard Codes of Practice:-
BS 5440:1:1990 Flues
BS 5449:1990 Forced circulation hot water systems
BS 5546:1990 Installation of hot water supplies for domestic purposes
BS 6700:1987 Design, installation, testing and maintenance of services supplying water
BS 6798:1987 Installation of gas fired hot water boilers
BS 6891:1989 Gas installation
BS 7593:1992 Code of Practice for treatment of water in heating systems
BS 7671:1992 Requirements for electrical installations, IEE Wiring Regulations
If installation is in a timber framed building, refer to the British Gas publication 'Guide for Gas Installations in Timber Frame
Housing' reference DM2.
This appliance meets the requirements of IP44, ie degree of protection against moisture.
Failure to install this appliance correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the
law is complied with.
Manufacturer's instructions must NOT be taken in anyway as over-riding statutory obligations.
2
Alpha 240XP and 240XE - Contents/Introduction
856368918.002.png 856368918.003.png
2
TECHNICAL DATA
2.1
PERFORMANCE - NATURAL GAS
Central Heating
Heat Input
MAX.
28.63
97 700
23.3
79 500
9.6
3.84
10.6
4.24
2.74
96.76
MIN.
11.76
40 150
9.3
31 700
1.1
0.44
2.1
0.84
1.13
39.9
Domestic Hot Water
Heat Input
MAX.
28.63
97 700
23.3
79 500
9.6
3.84
10.6
4.24
2.74
96.76
9.5
2.1
MIN.
11.76
40 150
9.3
31 700
1.1
0.44
2.1
0.84
1.13
39.9
kW
kW
(Gross)
Btu/h
(Gross)
Btu/h
Heat Output (modulating)
kW
Btu/h
Output to Water (modulating)
kW
Btu/h
mbar
mbar
Burner Pressure
Burner Pressure
Room sealed chamber
panel fitted
Room sealed chamber
panel fitted
in wg
mbar
in wg
in wg
mbar
in wg
Settings
Settings
Room sealed chamber
panel removed
Room sealed chamber
panel removed
Gas Rate
m³/h
ft³/h
Gas Rate
m³/h
ft³/h
Flow Rate at 35°C Rise
L/min
G.P.M.
2.2
SYSTEM
Domestic Hot Water
Max. Mains Inlet Water Pressure
Min. Mains Water Pressure
Min. DHW Flow Rate
Mains Inlet Connection
DHW Outlet Connection
DHW Water Content
Outlet Water Temp. (Approx. max.) °C
°F
Central Heating (Sealed System)
Max. System Pressure
Min. System Pressure
Max. System temperature
Pressure Relief Valve Setting
Expansion Vessel Size (pre-charge press.)
Flow Connection
Return Connection
Relief Valve Connection
Recommended System Pressure (cold)
CH Water Temp. (Approx. max.)
3 bar
0.5 bar
82°C
3 bar (44 PSI)
8 L at 0.8 bar
22 mm
22 mm
15 mm
1.0 bar
82
180
8 bar
0.2 bar
2.5 l/min
15 mm
15 mm
0.17 L
62
144
°C
°F
2.3
COMPONENTS
2.4
INSTALLATION
Burner (15 blade)
Main Heat exchanger
DHW Heat Exchanger
Main Burner Injectors
Pilot Injector
Stainless steel
Copper
Stainless Steel
1.18 mm
0.27 mm
Epoxy coated
Aluminium
Min. Clearances for Servicing
Top
Bottom
Sides
Front
220 mm
250 mm
5 mm
450 mm
100 mm Dia.
115 mm
107 mm Dia.
39 kg
(240XP only)
Flue Terminal Size
Flue Terminal Protruding
Hole Size Required For Flue Assy.
Lift Weight
Flue - Outer Duct
Flue - Inner Duct
Alpha 240XP and 240XE - Technical Data
3
856368918.004.png 856368918.005.png 856368918.006.png
 
2.5
GENERAL
2.6
ELECTRICAL
Dimensions
Height
Width
Depth
900 mm
450 mm
360 mm
22 mm
1.7 L
100 mm
60 mm
Supply
External Fuse
Power Consumption
Internal Fuse
Electrode Spark Gap 240XP
240XE
Thermocouple (240XP only):-
min. closed circuit output
230/240 V ~ 50 Hz
3 A
170 W
F2 A
5 mm
3.0 to 3.5 mm
Gas Connection
Primary Water Content
Air Duct Diameter
Flue Duct Diameter
10 mV
2.7
FLUE LENGTHS
Flue length = 0.75 m (not including the terminal, which is supplied with the boiler)
Note: Additional flues (of the same length) are available.
Length of Flue Required:-
Rear Flue = wall thickness +150 mm
Side Flue = wall thickness + distance between wall and side of boiler + 185 mm
Vertical Flue = distance from top of boiler side panel to required roof position minus 1 m for vertical terminal assembly
Maximum flue length = 4 m
Each additional 90° Bend is equivalent to 1 m of flue length
Each 45° Bend is equivalent to 0.5 m of flue length
The Vertical Flue terminal assembly is equivalent to 1 m of flue length
2.8
AVAILABLE PUMP HEAD FOR CENTRAL HEATING
Pressure loss across boiler
Output
Available pump head
Flow rate
kW
Btu/h
17°C
20°C
17°C
20°C
17°C
20°C
metres
feet
metres
feet
metres
litre/min
18.10
14.80
gal/min
4.00
3.27
litre/min
15.10
12.60
gal/min
3.32
2.78
feet
7.4
metres
2.33
3.00
feet
7.7
9.8
2.95
3.45
3.75
9.7
11.3
12.3
2.50
2.20
2.00
8.2
7.2
6.6
2.25
2.00
1.75
23.3
17.58
79 500
60 000
6.6
5.7
4.9
4.4
12.36
9.89
7.84
2.72
2.18
1.73
10.50
8.40
6.70
2.32
1.85
1.47
14.65
11.63
9.3
50 000
40 000
31 700
3.45
3.85
4.20
11.3
12.6
13.8
4.05
4.35
13.3
14.3
1.70
1.45
5.6
4.8
1.50
1.35
This information is based on 17°C and 20°C system design temperature difference.
2.9 ELECTRICAL CONNECTIONS
Note: This Appliance Must Be Earthed
An optional integral Clock kit is available if required.
Not
Used
Black
Wire
Black
Wire
Brown
Wire
Blue
Wire
5
4
3
2
1
Internal Clock Terminals
WARNING
1. Ensure wires are connected
correctly
2. Only fit the Alpha recommended
clock. Other clocks could cause
damage.
Clock connections
Boiler terminal block
Fig. 1
4
Alpha 240XP and 240XE - Technical Data
856368918.007.png 856368918.008.png 856368918.009.png 856368918.010.png 856368918.011.png 856368918.012.png 856368918.013.png 856368918.014.png 856368918.015.png 856368918.016.png 856368918.017.png 856368918.018.png 856368918.019.png 856368918.020.png 856368918.021.png 856368918.022.png 856368918.023.png 856368918.024.png 856368918.025.png 856368918.026.png 856368918.027.png 856368918.028.png 856368918.029.png 856368918.030.png 856368918.031.png 856368918.032.png 856368918.033.png 856368918.034.png 856368918.035.png 856368918.036.png 856368918.037.png 856368918.038.png 856368918.039.png 856368918.040.png 856368918.041.png 856368918.042.png 856368918.043.png 856368918.044.png 856368918.045.png 856368918.046.png
 
BOILER SCHEMATIC - Alpha 240XP
2.10
1
-
Pressure gauge
2
-
Gas service cock
3
-
Mains inlet on/off valve and filter
4
-
Diverter valve assy.
5
-
DHW flow valve
6
-
Primary flow valve
7
-
Differential pressure sensor
8
-
Automatic by-pass
9
-
DHW heat exchanger
10
-
DHW expansion device (if fitted)
11
-
Drain point
12
-
Pressure relief valve
13
-
DHW flow valve microswitch
14
-
Primary flow valve microswitch
15
-
Pump and air separator
16
-
Automatic air vent
17
-
DHW temperature sensor
18
-
Primary temperature sensor
19
-
Overheat thermostat
20
-
Expansion vessel
21
-
Gas valve
22
-
Main burner injector
23
-
Main burner
24
-
Pilot burner
25
-
Thermocouple
26
-
Main heat exchanger
27
-
Flue hood
28
-
Fan
29
-
Air pressure switch
30
-
Positive pressure point
31
-
Negative pressure point
32
-
Flue adaptor
33
-
Flue sample point
34
-
Room sealed chamber
35
-
On/off valve
36
-
On/off valve and filter
Heating
Flow
Domestic
Hot Water
Outlet
Gas
Cold Mains
Water Inlet
Heating
Return
Fig. 2
Alpha 240XP and 240XE - Technical Data
5
856368918.047.png